When wiring several motorized blind motors, you can’t simply link them all together — you need to calculate the current correctly for both the cable and the circuit breaker (CB), to prevent overheating, short circuits or nuisance tripping.
A real-world example
Motor current draw: 1 A per unit
Cable: THW 2.5 mm² Maximum current capacity approx. 16A
Recommended breaker: CB 16A
If you use several motors, refer to this table:
How many motors can be linked, by cable size
| Cable size (THW) | Max current (A) | Motors that can be linked (1 A each) | Recommended CB size | Note |
|---|---|---|---|---|
| 2.5 mm² | 16A | Up to 8 | 16A | Allow 50% load headroom |
| 4.0 mm² | 22A | Up to 12 | 20A–25A | Allows longer cable runs |
| 6.0 mm² | 30A | Up to 16 | 25A–32A | Suitable for combined cable runs |
| 10.0 mm² | 40A | Up to 25 | 32A–40A | For large combined systems |
Advice: Allow about 25–50% load headroom to prevent cables overheating and keep the breaker working accurately.
Cable length causes voltage drop — use a larger cable for runs over 20 metres.





